Building Inspection Guide
Copyright 2000 / 2001 André J. Béïque
~ All rights reserved ~
Attic ventilation and the vents commonly used
|
|
What's New? | Discussion Forum | Table of Contents | Subject Index | Glossary | Contact for an Inspection | Français |
|---|---|---|---|---|---|---|---|
![]()
Last
modification: Wednesday August 28 2001
The principle: Heat and cold control by air circulation in the attic.
In winter, the intent is to keep the heat inside and the cold outside. In summer, it is to keep the cold inside and the heat outside. Before the availability of modern insulation, attics where sealed as much as possible and there was no air circulation.
The results: Heat accumulation in the attics.
With the accumulation of heat
in the attic in summer, there was a rapid deterioration of
the roofs and the top floor of buildings was extremely
warm.
Condensation and frost
developed in the attic in winter and the humidity froze at
the perimeter walls at the attic level. Sometimes, the
humidity descended behind the brick walls turning them
white with efflorescence and then, there was a
deterioration of the bricks themselves and of the mortar
joints would pop-out.
Brick joints had to be
re-pointed with mortar every 10 to 15
years.
The overheating of the attic and roof was worse if there was not a good thickness of crushed stone laid on the impervious membrane to dissipate the sun heat. This situation often leaded to have to change the roof.
The improvements: Availability of modern insulation.
With the invention and manufacturing of modern insulation, it gave the possibility to insulate the attics from the cold in winter and from the heat in summer.
The result: Possibility to have air circulation in the attic
Now it was possible to vent properly the attics to dissipate the heat in summer and in winter, to circulate air in the attic to vent out the humidity. This humidity freezing behind the brick was the cause of the brick joints to pop out and of the whitening of brick walls called "Efflorescence".
This
section describes the vents
needed to permit proper air circulation in the
attics to dissipate heat and humidity.
![]()
Section 1 - The Ridge Outlet Vents.
A - The
goose-necks
B - The
turbines
C - The
louvered towers
D - The
continuous ridge vents
E - The flat
individual vents
F - The hay
barn ridge vents
G - The
architectural vents
H - The
ridge dormers with a triangular louvered
vent.
I - The top
of the vertical wall grate outlet vents
J - No ridge
air outlet vents
![]()
Section 2. - The Soffits Inlet Vents.
A - Soffits with air inlet
grates
B - Soffits
with perforated aluminum as air inlet
C - Soffits
with insufficient grates as air inlets
D - Soffits
with no air inlets
E - The
plain wall with no soffit or air
inlet
![]()
Section 3. - The Cornice Inlet Vents
A - The
cornice with grate inlets
B - The
cornice with continuous slot and screen
C - The
cornice with perforated aluminum used as air
inlet
D - The
cornice with no air inlet grates
E - The
cornice of decorative granite
F - The
cornice of decorative metal
G - The
cornice of decorative wood without air
inlets
![]()
Section 4 - The Wall air Inlet Vents.
A - The hooded
inlets
B - The
grate inlets
C - The one
brick replacement inlet
D - The big
grates where there is also decorative granite
cornice
![]()
Click photos for an enlarged view,
then
back.
Section 1 - The Ridge Outlet Vents.
A - The Gooseneck outlet
Vent.
a) The Goose Neck is the outlet vent normally used on flat roofs.
B - The turbine outlet vent.
a) The
wind spins the turbine to keep
rain and snow out by centrifugal
force.
It happens that if there is no wind or if freezing rain
freeze-up the turbine; by not spinning, snows or rain may
come through the turbine openings that are quite
large.
The turbine became very popular in the 1970's and 80's and
is now more and more replaced by other kind of ridge
vents.
It is to be
noticed that there is no formation of ice at the edge of
the roof. The soffits are opened and the air circulates
properly through the attic.
C - The circular louvered outlet vent replacing turbines.
a) This louvered circular outlet vent is static as it has no part in movement.
This vent is replacing the turbines. It is
interesting that the shape and size are the same as the
bottom part through the roof that was used by the
turbines.
Turbines eventually also make noise when the bearings wear
out.
Turbines have been found to freeze during ice storms. The
only reason for the turbine to turn was to use the
centrifugal force generated by the wind to eject rain, snow
and ice.
b) - A second type of circular ridge vent.
In the clicked enlargement, it can be seen that this outlet
alone is insufficient to circulate the heat lost.
The soffit is blocked. There are no air inlet grates or
perforated soffit. In winter, the heat lost entrapped in
the attic melts the snow on the roof and creates
icicles.
It is the same principle as closing the damper on a 30
foot chimney. Air cannot go in and out by the same
opening.
c) - The more modern square louvered ridge vent.
It has been found that there is never too much ventilation
of attics. These louvered square vent chimneys are very
efficient and are static.
On single family homes, two units are installed at the
ridge. Individual units installed 20' feet apart are
sufficient in number.
D - The continuous ridge
vents
| Here are patented continuous ridge vents. | ||
|---|---|---|
|
|
|
| This is a Patented ridge vent of very good design | This one also. | And a third type of continuoust ridge vent. |
E - The flat individual
vents
a) - The flat outlet vents where one of the first type used to vent attics.
There
is a tube of eight (8") to ten (10") inch diameter under a
cap opened on the 2 sides and bottom. Normally one used
every 10 to 15 feet apart at
the ridge.
b) - In this photo, used as ridge vents and as vents for side triangular attics on the second floor.
It is
one of the only kind of vent that is low and strong enough
to be installed on the middle or bottom slopes of roofs and
not be thorn out by packs of snow and ice slipping down the
roof.
c) - Here used as ridge vents on a church roof.
On major size roofs, it is common to have these
outlet vents installed on each side of the roofs venting
the same attic.
F - The hay barn vents
a) - The tower louvered outlets where huge. They had to circulate enough air to dry and keep dry the hay.
G - The architectural
vents.
a) - These tower louvered outlets often used on major buildings are almost a copy of the barn tower ridge vents.
H - The ridge dormer
vents.
a) - Instead of having a window in the dormer, there is a triangular louvered vent with a back screen. It is sometimes used on roofs of churches as ridge vents. The pointed ridge of the dormer vent resists better to ice sliding down sloped metal roofs.
One dormer vent on each slope would have seem sufficient to
vent the attic, sometimes some components become
architectural design or esthetics.
b) - Here is an enlargement of the right one. Materials used are strong and rigid as ridge vents.
If a pack of ice slides down the metal roof, these vents
would not be ripped off.
c) - Finally, the dormer vent used on a church as ridge vents.
The proportion of air vent to the size of roof is very
different. The same kind of vent is used on the other slope
of the roof which is sufficient as outlet at ridge of the
attic for a good air circulation.
I - The vertical wall ridge
vents
a) - They where used originally as the only vents at the top of attics. One at each end of the attic. If there was no wind, there was no air circulation in the attic.
This is a gable roof. The attic vent can be seen at the
right of the chimney. In most of these design outlets, air
does not come in by the lower soffits.
The solution is to add ridge tower vent at the top of the
back slope of the house as outlet vents and these
rectangular vents become the intake to the attic. Then
there is a good air circulation in the attic.
J - No ridge vents
a) - Here what happens when there are no ridge vents. It is worse if there are no soffit and a lack of insulation.
As it can be seen, there are no ridge
vents. In other photos where two neighboring properties can
be seen, the snow melts first on this roof at temperature
well below the freezing point.
There are no ridge nor soffit vents in this property. When
this property was built, insulation materials did not exist
except 3/4" inch thick cardboard.
Section 2. - The soffit is the horizontal part under the roof edges.
A - Soffits with grate
Inlets
a) In the past, grates of all kind where installed in the wooden soffits.
B - Soffits with perforated aluminum
Inlet.
a) Now, there are aluminum soffits.
This
property has a good wide soffit all around the
house.
It would be
an error to completely block the wide soffit by laying
insulation from inside the attic on the inside side of the
soffit. It would block the ventilation and keep heat and
humidity inside the attic. A soffit is like a damper on a
fireplace. It needs to be opened.
b) - This property has also Aluminum perforated soffits on the whole length of the building. The roof above the balconies has the edge of the ceiling opened as soffit inlets.
When
the top of brick walls, right under the soffit, is in
perfect condition, it is because the soffit is functional
and there are gooseneck vents on the roof.
C - Soffits with insufficient grates
as air inlets
a) Some attics have soffit inlet and ridge outlets. It has been found that some grate inlets are too small to let sufficient air in the attic.
The inlet grates in the soffit are too small and snow on
the roof still melts and produces icicles. The heat lost in
the attic is not dissipated.
b) There is a lack of insulation plus a bad communication between the soffit air inlets and the 2 ridge square vented towers.
The solution is to add more grates or to make a
four (4") inches wide slot all along the wooden soffit and
cover with a brown aluminum soffit with the bigger size
holes normally used on the underside of balconies.
c) - Some vents are much too small and limited in number.
Now,
full perforated soffits are used. If there are icicles, the
3 only causes are a lack of inlets, a lack of outlets, a
lack of insulation. One, two or all of these situations are
enough to melt the snow on a roof.
D - Soffits with no air
inlets
a) It was often thought that this kind of soffit extension where simply architectural. The architects designed them originally to install air inlets into. Contractors who built the houses sometimes did not understand the function of the roof extension or it may have been up to the owner to add the grates.
| These older properties have no air inlet grates or slots to let the air in their attics. | ||
|---|---|---|
|
|
|
|
|
There are
no inlet grates installed in the soffit to let air in
the attic. There is then very little air circulation
in the attic even if there is goose-necks on the
roof. Some hot air will still be replaced by cold air
replacement to avoid vacuum when the heat lost will
rise out of the attic by the goose-necks.
It is the same principle as leaving the damper of a fireplace opened in winter. |
The
entrapped humidity in the attic makes the paint scale
and eventually the wood rots where there should
have been a grate inlet installed.
Older buildings had sealed attics as there was no insulation available. |
This
is the most important photo of all
for information. The wind has blown off part
of the soffit, the metal facia and some of the
shingles.
It is taught that
the moment there is a metal perforated soffit
installed, there are air inlets to the
attic! |
c) There is a soffit, but without air inlets, there is no air circulation. It is worse when there are no ridge vent and insufficient insulation in the attic as in this case.
| This is the same property at different times. | ||
|---|---|---|
|
|
|
|
| Water freezes even on the wall and sill | and on the window and frame. | Efflorescence is appearing under the sill. |
d) The soffit has a slight slope toward the wall.
The same property at different times. The icicles are
getting longer and more ice has developed on the left side
of the window.
e) Interesting to see the size and length of the icicles in relation to the window
Again at different times. There are no ridge
vents, no soffit vents and no insulation in the attic.
E - The plain wall with no soffit or
air inlet
a) When there are no architectural features to install air inlets.
Every 15 to 20 years, the joints need to be redone
if there is no ventilation of the attic.
b) Around 1928, there was a roof edge that was very popular. It had an overhanging roof with no horizontal roof edge soffit for air inlet.
If the underside of the roof was followed,
eventually the brick wall would be encountered with no
opening vent inlet to the attic.
Modern insulation did not exist. Most attics where sealed
to create a thermos as much as possible. A floor made of
tongues and grooves boards would partially add to the
thickness of the ceiling inside. Some had saw dust between
the beams.
Note: See the section on walls:
Section 3 - The in wall cornices used when there is no soffit.
A - Cornice with grate inlet vents.
B - The cornice with continuous screen
a) The cornice with continuous screen wall air inlet vent.
Full length in wall cornice used as
air inlet to the attic replacing the soffit
architectural design.
This double slotted cornice had a screen to stop birds,
bees, squirrels from entering the attic. This roof will
never overheat in summer at the condition there are also
gooseneck vents to let the air out.
C - The cornice with perforated aluminum inlet
a) Full length in wall cornice used as air inlet to the attic replacing the soffit architectural design.
Here is a good design for a continuous wall cornice
to let the air in the attic.
The air does go in the soffit of this cornice.
D - The cornice with no air inlets
a) Partial wall cornice supposed to be used as air inlet to the attic.
Again these cornices may have been simply
decorative in the past. Because of the height of the attic
and the sloped roof that gives more height at the four
corners it is possible to insulate the attic and add grate
inlets to the cornices.
E - The cornice of decorative granite
a) A granite cornice used in the architectural design. The attics of buildings of this age where not vented.
On the enlargement, it can be seen that there is the
formation of efflorescence on the bricks. This is the
indication of a lack of ventilation. The humidity is
trapped in the attic and eventually lies on the inside of
the brick wall. Eventually, the mortar between the bricks
pop's out pushed by frost.
b) An other granite cornice used in architectural design.
No air inlets in the facade. On the side past the
chimney, there is one hooded wall inlet to the attic. There
are still not enough air inlets. That is why the mortar
between the bricks above the cornice had to be
re-pointed.
c) Some designs may be considered more extreme having both huge grate inlets and architectural granite cornices.
There are big air inlet grates to the attic. There are also
two granite decorative cornices in this design. Huge grate
inlets are intakes for circulating air in the attic in
replacement of having the cornice designed with air
inlets.
F - The cornice of
decorative metal
a) Some cornices where made of metal.
b) This is a higher attic with a metal decorative cornice.
The white paint is scaling off the metal as the humidity
behind the cornice freeze in winter. The cornice being
decorative and not functional, the brick joints had to be
redone as the trapped humidity pushed out the mortar at the
top of the wall.
In the enlarged photo it can be seen that it is a double
brick wall. A double brick wall normally has the bricks
seen on their end every six or seven row.
On that particular row, it can be seen that at every next
brick, there is one seen on it's end.
G - The cornice of decorative wood
a) There are no inlet grates installed in the white wood.
The darken granite can simply be washed with soap and a
good floor brush. The dirt is not washed off by the rain as
it is under the cornice.
b) During the first part of the century, there was more detailing in the designs of wood works. More precisely before the depression of 1930.
This
is a good architectural design for a cornice, but there is
no inlet vents to the attic.
c) Many older buildings had extensive soffits called cornices which could
extend many feet down the front
walls.
This cornice has the horizontal soffit perforated
with small holes used as air inlets to the attic.
![]()
Section 4. - The vertical wall inlets used when there is no soffit.
A - The hooded inlets
a) The single wall air inlet vent to the attic.
b) Here is the perfect air inlet ventilation for a vertical wall. Normally used on the side walls of homes where there is no soffit or cornice. This wall is in perfect condition.
With sufficient wall inlets, the attic is properly
vented.
B - The grate inlets
b) Here is a very big grate used as air inlet to the attic. There is also not one, but two decorative granite cornices.
When these kind of huge grates are used on four walls, the
flow of air through the attic may be so important that rain
and snow may be pulled in the attic. An inverted hood is
then installed as a baffle on the inside of the attic.
C - The one brick replacement inlet.
a) These vents are the dimension of one brick and are set every 10 to 15 feet apart at the level of the attic.
| The One (1) brick wall inlet to the attics. | ||
|---|---|---|
|
|
|
|
| There is grates having the dimension of one brick that is used to vent triangular attics at the level of the bedrooms. These may be used in conjunction with flat vents on the roofs. |
A brick
is replaced by a grate inlet where there has been a
problem of humidity discoloring the walls and
creating efflorescence in brick walls. They
should be installed not more than 10' to 15' feet
apart.
|
In many buildings, this grate is added when there is a need to add ventilation to an attic when the attic is very small or has almost no height. In this wall, as the attic is high, a hooded grate inlet could have been used. |
In Conclusion
The most important part of this section is: Is there a slot cut out hidden behind an aluminum perforated soffit?
It is something to check in our own home using a wire or a tool with a fine point.
If there is bubbles of tar protruding from the crushed stones on the roof, there is great chances that there is not any slot behind the perforated metal soffit.
What is to be done is explained during a building inspection.
Since May 5, 2001 |
||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|